IEC 61850, the global standard for communication in substations, is bringing open, Interoperable, systems, and flexible architectures, to the substation automation domain. Today's power utilities operate more globally and require flexible, future-proof systems to cope with changing requirements, philosophies, and technologies.
IEC61850-3 Industrial Ethernet Switch
Intelligent Gateway for IED integration
Precise Time Synchronization Soltuion
IEC61850-3 Industrial Ethernet Switch
Wide product range: Modularly designed rack mount switches and DIN-Rail models with high voltage input
Compliant with IEC61850-3 and IEEE 1613
Supports NTP, precise time sync IEEE1588v2 and ITU-T.G.8261/G.8262 (Sync-E)
Supports redundancy protocols: IEC62439-3(HSR/PRP), IEC62439-6(DRP), DT-Ring family, RSTP
Multi-service platform for switches and time server with GPS and IRIG-B modules
Built-in IEC61850 data modeling with MMS server for device management
Supports legacy RS232/485/422 serial connections combined with data switching
Intelligent Gateway for IED integration
Supports data collection from both legacy IEDs and IEC61850 IEDs with ethernet and serial connections
Easy configuration by importing standard .CID files
Supports protocols: IEC60870-5-101, IEC60870-5-102 (master), IEC60870-5-103 (master - slave), IEC60807-5-104 (master - slave), MODBUS (master -slave - RTU/TCP), DNP 3.0 (master - slave - serial/over TCP/IP), SEL (master -fast meter/SER), AREVA (master - courier)
Supports BRCB and URCB reports, GOOSE messaging, MMS file transmissions and IEC61850 modules
Precise Time Synchronization Soltuion
Product portfolio includes time server, IEEE1588v2 Switch, clock converter, time test instrument
High precision time server with 100ns accuracy with multiple reference satellite systems: GPS, BD, GLONASS
Supports multiple reference source switchover within 200ns
Different oscillator options support holdover performance up to 1us/1h
IEEE1588 to IRIG-B conversion device for backward compatibility
Reliable multiple source selection algorithm and holdover performance
Optional management protocols of MMS/IEC60870-5-104/SNMP for time server
Compliant with IEEE PC 37.238 Power Profile